Products

MOEORW-YJ500D AC Sampling Tester Send email to us

Applications

Product Overview
    The MOEORW-YJ500D AC Sampling Tester is developed in accordance with JJG126-95 “Electrical Measurement Transducer for Converting AC Quantities to DC Quantities,” DL/T630-1997 “Technical Specifications for AC Sampling Remote Terminal Units,” and GB/T 13729-2002 “Standard for Remote Terminal Units.”  
    It incorporates large-scale imported integrated circuits, a high-speed digital signal processor (DSP), DDS waveform synthesis, a complex programmable logic array (CPLD), a large-scale integrated amplifier, and a user-friendly operating system.
    Suitable for the verification and calibration of AC sampling devices, transmitters, and indicating instruments, it serves as an ideal equipment for product verification and calibration in industrial and mining enterprises as well as power systems.

Features

• Features a wide-band standard source design with high output power, exceptional stability, and rapid response.
• Integrates system, testing, and signal generation into a single module, delivering high integration, low failure rate, compact size, lightweight construction, and superior reliability.
• Simple operating system displays test screens immediately upon startup. Standard source output requires no guidance programs, ensuring fast response and high efficiency.
• Superior closed-loop output for voltage, current, power, phase, and frequency. Software calibration enables one-time point setting for user-friendly operation.
• Pre-set common test points for voltage, current, and phase simplify operation with one-point adjustment, ensuring convenience and efficiency.
• Utilizing power communication protocols and computers, the calibration device conveniently performs fully automated verification and management of AC sampling devices and various transmitters.
• Flexible software functionality with domestic template-based protocol configuration and template-based report configuration allows users to customize new RTU communication protocols and report formats via templates. The software provides communication protocol templates for over a hundred common RTU models from major manufacturers, along with robust online help and voice prompts.
• Integrated meter-source design combines front-panel standard source output with rear-panel external standard input, unifying protocol verification and field calibration (with clamp meter) functions.
• Outputs standard harmonics from 2nd to 31st order, supporting single-harmonic or arbitrary multiple-harmonic superposition.
• Arbitrary phase shifting is possible between three-phase voltages, three-phase currents, and individual phase voltages/currents, enabling simulation of various power fault outputs.
• Multiple alarm and protection functions are provided. The device performs self-diagnostics for faults, displaying fault type and location for safe and • Equipped with interfaces and software. The interface protocol is open, allowing users to program and control the instrument independently.

Parameter

AC Output
2.1.1 Three-Phase AC Voltage Output
Range: 57.7V, 100V, 220V, 380V
Adjustment Range: (0–120)% RG1
Adjustment Resolution: 0.002% RG
Accuracy: 0.05% RG
Stability: 0.01%/2 min
Distortion:            ≤0.2% (non-capacitive load)
Output Load:            35VA per phase
2.1.2 Three-Phase AC Current Output
Range:              1A, 2A, 5A, 20A
Adjustment Range:      (0~120)%RG
Adjustment Resolution:  0.002%RG
Accuracy:            0.05%RG;
Stability:            0.01%/2min
Distortion:            ≤0.2% (non-capacitive load)
Output Load:          25VA per phase
2.1.3  Power Output
Active Power Accuracy: 0.05%RG
Reactive Power Accuracy: 0.1%RG
Stability:            0.01%/2min
2.1.4  Phase Output
Adjustment Range: 0° to 359.99°
Resolution: 0.01°
Accuracy: 0.05°
2.1.5 Power Factor
Adjustment Range: -1 to 0 to +1
Resolution: 0.0001
Accuracy: 0.05%
2.1.6 Frequency Output
Adjustment Range: 45Hz to 65Hz
Resolution: 0.001Hz
Accuracy: 0.002Hz
2.1.7 Three-Phase Voltage, Current Symmetry, and Phase Symmetry
Voltage/Current Symmetry: ≤0.02%
Phase Symmetry: ≤0.05°
2.1.8 Voltage and Current Harmonic Output
Harmonic Order: 2 to 31
Harmonic Content: 0 to 40%
Harmonic Phase: 0 to 359.99°
2.2 AC Measurement
2.2.1 Three-Phase AC Voltage Measurement
Range: Auto-ranging (57.7V, 100V, 220V, 380V)
Measurement Range: (0–120) %RG
Resolution: 0.01%RG
Accuracy: 0.05%RG
2.2.2 Three-Phase AC Current Measurement
Range: 5A
Measurement Range: (0–120)%RG
Resolution: 0.01%RG
Accuracy (terminal input):    0.05%RG
Accuracy (clamp input):    0.2%RG
2.2.3  Power Measurement
Active Power Accuracy (terminal input):    0.05%RG
Active Power Accuracy (clamp input):    0.2%RG
Reactive Accuracy (Terminal Input): 0.1% of Reading
Reactive Accuracy (Clamp Input): 0.5% of Reading
2.3 DC Output
2.3.1 DC Voltage Output
Voltage Range: 75mV, 10V, 100V, 300V, 600V
Output Range:               (0~120)%RG
Accuracy:                0.05%RG2
Stability:                0.01%/1min
Ripple Content:                ≤0.5%
Regulation Fineness:                0.002%RG
Output Load:                10VA3
 2.3.2 DC Current Output
Current Range:                20mA, 10mA, 1mA
Output Range:               (0~120)%RG
Accuracy:                0.05%RG
Stability:                0.01%/1min
Ripple Content:                ≤0.5%
Adjustment Resolution: 0.002% of Full Scale
Output Load: Maximum output voltage 40V
2.4 DC Input
2.4.1 DC Voltage Input
Voltage Range: ±10V, ±5V, ±2.5V
Measurement Range: (0 to 120)% of Full Scale
Accuracy: 0.01% of Full Scale
2.4.2 DC Current Input
Current Range: ±20mA, ±10mA, ±5mA, ±1mA
Measurement Range: (0~120)%RG
Accuracy: 0.01%RG

After-sales guarantee

  • Free technical advice

    We provide you with free consultation services

  • On-site installation and commissioning

    Engineers provide guidance for installation and commissioning

  • Free training and maintenance

    Technicians can provide on-site maintenance services and receive regular training

  • Perfect after-sales services

    Perfect technical consulting service system

Workshop site

Video Center

Engineering Cases

Related products

Related articles

Send your message to us:

Leave Your Message