Overview
This device is designed for online monitoring of system-to-ground insulation performance in China's energy storage and new energy vehicle sectors, based on actual operating conditions. Suitable for ungrounded systems rated up to DC 1150V, it meets insulation monitoring requirements for most energy storage, charging station, and new energy applications.
Employing a low-frequency AC injection method, this device reliably and accurately monitors the following parameters for DC and IT (ungrounded) systems: system insulation resistance to ground, system capacitance, bus voltage, positive and negative voltages to ground, positive and negative insulation resistances to ground. Alarm event logs and other parameters can be remotely transmitted to a host computer via the 485 protocol. Various measurement conditions selectable from the settings menu allow for optimized adaptation to specific application measurement techniques.
During operation, the insulation monitor continuously monitors the insulation resistance of the entire IT system. An alarm is triggered when this value falls below a preset response threshold. The device must be connected between the IT system (ungrounded system) and the PE line to obtain measurement values. A microcontroller records and measures values in the microampere range superimposed on the system.
l Suitable for ungrounded main circuit systems rated up to DC 1150V.
l Built-in/external test/reset buttons.
l Automatic and manual reset functions.
l Multi-type, wide-range control power input.
l User-friendly interface displaying various parameters and system leakage capacitance.
l DIN rail mounting.
l Backlit LCD display.
l Communication capability to read positive-to-ground, negative-to-ground voltages, and insulation resistance values.
l Measurement and display of insulation resistance in ungrounded systems.
l Measurement and display of leakage capacitance (C).
l Communication via Modbus RS-485.
l Adjustable response delay
l Two independent alarm relays (each with one changeover contact)
l Selectable N/O or N/C operation
l Supports Chinese and English language menu operation
|
IT systems that meet monitoring requirements |
IT system rated voltage (operating range ) |
DC 1150V (0 ~ 1150V) |
|
Auxiliary power supply |
Voltage |
AC 85~265V (45~65Hz) DC 18~36V |
|
Power consumption |
≤6 W |
|
|
alarm value |
Alarm value Ran1 (Alarm 1) |
1KΩ ... 20MΩ |
|
Alarm value Ran2 (Alarm 2) |
1KΩ ... 20MΩ |
|
|
Response time |
t1 at RF = 0.5 x Ran and Ce = 1 μF |
≤ 4 s |
|
Insulation alarm delay t on |
0…9999s |
|
|
IT system measurement circuit |
Measured voltage U1 |
± 60V |
|
internal resistance R1 |
≥ 600kΩ |
|
|
Impedance Z at 50Hz |
≥ 600kΩ |
|
|
Permissible system leakage capacitance Ce |
≤ 500 μF |
|
|
Display range of measured values |
1KΩ ... 20MΩ |
|
|
Measurement error 10KΩ...20MΩ |
±15% |
|
|
password |
off/0…999 (off) |
|
|
Fault Log |
1 28 articles |
|
|
Fault memory, alarm relay |
switch |
|
|
Measure the number of filtrations |
The number of filters can be set from 1 to 10. |
|
|
digital input |
1 trunk node |
Built-in DC15V power supply |
|
Switch output |
2-channel relay |
1 normally open, 1 normally open , 1 normally closed |
|
Communication Group 1 |
R S485 1 |
Communication protocol : Modbus RTU Communication speed : 2400-38400bps |
|
liquid crystal |
128*64 dot matrix |
|
|
Wiring capability |
RS485 |
Twisted pair shielded cable 0.2…2.5 mm² |
|
Measurement wiring |
0.2…2.5 mm² |
|
|
Mechanical properties |
weight |
0.2KG |
|
Protection level |
IP20 |
|
|
External dimensions |
100×72×66mm |
|
|
Housing material |
PC+ABS |
|
|
Work Environment |
Operating temperature |
-20℃~55℃ |
|
Storage temperature |
-30℃~70℃ |
|
|
altitude |
≤ 2000m |
|
|
Insulation withstand voltage |
AC4000V |
We provide you with free consultation services
Engineers provide guidance for installation and commissioning
Technicians can provide on-site maintenance services and receive regular training
Perfect technical consulting service system