Products

MEZRC-III(20A) Transformer DC resistance meter Send email to us

Applications

Overview

     The measurement of transformer DC resistance is a must-measure item in transformer manufacturing, outgoing tests of semi-finished products and finished products, installation handover tests, and preventive tests of power departments. It can effectively detect manufacturing defects such as material selection, welding, and loose connection parts, missing strands, and broken wires of coils, as well as hidden dangers that exist after operation. The MEZRC-III (20A) three-channel DC resistance tester is a quick testing device for the DC resistance of transformer, mutual inductor, generator, and motor windings. It is especially suitable for simultaneous three-phase measurement of large capacity star connected transformers, which saves time and improves maintenance efficiency.

Features

 Three-phase simultaneous measurement is possible for transformers with neutral points, greatly saving measurement time.
 The instrument has a demagnetization, which can eliminate residual magnetism at one time.
 The instrument has a wide range of resistance measurement and high resolution, with multiple current gear options.
 The instrument a perfect back-EMF protection function.
 Longitudinal testing of the DC resistance of a transformer with load tap changer can be completed at one time.
 The has high measurement accuracy and features anti-interference, shock resistance, and portability.
 A 5.0-inch 65K color touch screen is used easy operation.
 Built-in large capacity non-volatile memory can store 500 sets of data.
 Built-in high-speed micro thermal printer can measurement data.
 Built-in high-precision clock displays real-time time.
 USB storage function.

Parameter

Three-phase test :

Test current

Test scope

Accuracy

10 A + 10 A (2 * 10)

500 μΩ ~ 0.5 Ω​

± (0.2% of reading + 1.0 μΩ)

5 A + 5 A (2*5)

1mΩ ~ 1Ω​

± (0.2% of the reading + 0.01 mΩ)

1 A + 1 A (2*1)

50 mΩ ~ 10 Ω

± (0.2% of the reading + 0.1 mΩ)

0.1A + 0.1A ( 2 * 0.1 )

500 mΩ ~ 50 Ω​

± (0.2% of the reading + 0.001Ω)

 
 

Single- phase test :

Test current

Test scope

Accuracy

20A

250 μΩ ~ 1.0Ω​​

± (0.2% reading + 0.5 μΩ)

10A

500 μΩ ~ 2.0Ω

± (0.2% of the reading + 0.002 mΩ)

5A

10 mΩ ~ 4.0 Ω

± (0.2% of the reading + 0.05 mΩ)

1 A

50 mΩ ~ 20 Ω

± (0.2% of the reading + 0.1 mΩ )

0.1A

500 mΩ ~200 Ω

± (0.2% of the reading + 0.001Ω)

Resolution: 0.0001 μΩ , 5 significant digits

Main unit dimensions: 420mm × 250mm × 340mm

Main unit weight: 15kg

2. Usage conditions

Ambient temperature: -10℃ to 50℃

Ambient humidity: ≤85% RH, non-condensing

Operating power supply: AC220V ±10%

After-sales guarantee

  • Free technical advice

    We provide you with free consultation services

  • On-site installation and commissioning

    Engineers provide guidance for installation and commissioning

  • Free training and maintenance

    Technicians can provide on-site maintenance services and receive regular training

  • Perfect after-sales services

    Perfect technical consulting service system

Workshop site

Video Center

Engineering Cases

Related products

Related articles

Send your message to us:

Leave Your Message